How are pressure and temperature read together in a steam line?

Short answer

For a steam hose, pressure and temperature must be read together. Saturated steam has a pressure-temperature relationship; a higher temperature at the same pressure can indicate a different steam state. The pressure reference and the product's saturated/superheated steam scope must be clear.

Source: S022, S036

Technical explanation

It is not correct to read the maximum pressure and temperature figures in a hose catalog as two independent approvals. The product may be designed for specific steam conditions. In addition, whether the steam table uses absolute or gauge pressure affects the result. In addition to normal production, commissioning, depressurization and shutdown conditions are also assessed. A table showing the thermodynamic relationship does not on its own prove that the selected hose can operate at that point; the product's service scope is also required.

Source: S022, S036

Topic-specific checkpoints

ItemDescription
PressureValue, unit, absolute/gauge reference and measurement point.
TemperatureFluid temperature in the same operating state.
Steam stateDefinition of the saturated, wet or superheated condition with process data.
Product scopeSuitability of the relevant model for the steam type and conditions.

Source: S022, S036

How is it assessed in practice?

In the selection file, keep the pressure value, its unit, reference and measurement point in separate fields. Tie the temperature to the same operating state. For example, if the pressure on the boiler display and the temperature at the hose inlet were taken at different times, the two should not be combined as a single verified operating point. Instead of sending only the two largest numbers to the manufacturer, communicate normal and transient states in a table. Do not close out an uncertain phase condition under the word 'steam'.

Original editorial recommendation; not a clause of a standard.

Frequently asked questions

Can I use the maximum temperature and pressure on the label together?

Do not assume this. Under which condition the two limits apply at the same time must be verified from the manufacturer's documentation.

Source: S022, S036

Source coverage

  1. S022
    DAMPF TRIX 6000 Continental · accessed 2026-10-19 Further properties; technical notes under product table
  2. S036
    Industrial Hose Safety Connections Gates · accessed 2026-10-19 PDF pp. 6–8 construction and selection; pp. 10–19 maintenance; pp. 21–27 special services